The working principle of control circuit of electric valve

Date : 2021-3-31 8:52:22

State selection

When the circuit in a hot standby state, you can select SA1, the switch position of SA2, determine the main circuit is controlled or uncontrolled. When SA1 (SA2) on the left, KM1 (KM2) coil exit; When SA1 (SA2) on the right, KM1 (KM2) of coil in operation. When SA1 (SA2) on the left, the signal light is lit, operating or maintenance personnel can use the block check whether the control circuit is electricity; When SA1 (SA2) on the right, the signal light is not bright, only after the motor start valve, the signal light HL1, HL2 spangle (HL3, HL4).

Open valve

Switch on the power switch QF, would choose SA1 placed in the right, press the SB1 (or SB2), current and in turn after V11 SB1 (or SB2) - KM2 of contact (2, 3) - - for SQ2 - SA1 KM1 coil - KH contact (7-9) - KM3 of contact (9, 10) - SB5 - W11, KM1 coil action and self-locking, valve motor rotation, open the valve. Contact in KM1 (5-6) after connecting, flash switch S1, red light flashing HL1 and green HL2. When the valve is open to the corresponding position, for SQ2 disconnect, KM1 lose electric coil, its main contactor reset, the power is cut off of the valve motor valve motor stop working.

The valve closed

Will select switch SA2 on the right, press SB3 (or SB4), current in turn after the V11 - SB3 (or SB4) - > contact of KM1 (13, 14) - KM2 coil - SQ1 to SA2, KH contact (7-9) - KM3 of contact (9, 10) - SB5 - W11, KM2 coil absorption merger self-locking, motor rotating valve, close the valve. Contact in KM2 (12-15) after connecting, flash switch S2, HL3 a red light and green light flashing HL4. When the valve is closed to the appropriate location, position switch SQ1 disconnect, KM2 of coil electricity, its main contactor reset, the power is cut off of the valve motor valve motor stop working.


Manually locate

In the process of open or close the valve, may at any time, press the stop button SB5 the normally closed contacts disconnect, make KM1 or KM2 coil lose electric release, motor power loss. At the same time, SB5 normally open contacts (19 - W11) closed, KM3 coil electricity and, their contact (9, 10) disconnect, prevent KM1 or KM2 misoperation, KM3 closure of the main contact, make the output of the bridge rectifier and capacitor energy storage effect in the winding of the motor at the same time, the braking torque, the motor instantaneous halt. In this way, can make the right to stop valve to the specified location.

Matters needing attention

Variable resistor RP current-limiting role in this diagram, through adjusting the RP braking current can be obtained, usually braking energy current 4.5 A. Electrolytic capacitor in the figure could be selected according to valve is the power of the motor, if the valve motor under 2 kw of power, can choose 1


 Recommended News
[2024-3-28] > cippe2024-北京
[2024-3-19] > 南海發現特大油田!

Partners

Partners

Contact Us

Contact Us

Copyright  ©  2021  YANCHENG BAIXIN PETROLEUM MACHINERY CO.,LTD.  All Rights Reserved  蘇ICP備11091237號  

蘇公網安備 32092502000202號

主站蜘蛛池模板: 在线观看你懂| 一区二区免费播放| 国产精品成人久久久久| 国内一级野外a一级毛片| 欧美一级特黄高清免费| 日朝欧美亚洲精品| 麻豆一区二区三区四区| 靠逼视频网站| 国产成人精品高清在线观看99| 成人高清在线| 黄色一级一毛片| 日韩成人在线网站| 亚洲欧美成人网| 欧美日韩亚洲一区二区| 99视频热| 日日好吊妞| jzzjlzz亚洲乱熟在线播放| 成人综合激情| 男人下面疯狂进女人下部视频| 欧美亚洲桃花综合| 一个人在线免费观看www| 免费一级a毛片在线播| 中文字幕在线乱人伦| 日韩欧美中文字幕在线观看| 成人夜夜| 亚洲韩国日本欧美一区二区三区| 日韩欧美第一页| 国产高清国产精品国产k| 在线观看欧美日韩| 久久线看观看精品香蕉国产| 色视频在线看| 欧美理论在线| a在线视频| 一级黄色片中国| www.伊人| 成年人网站免费| 久久免费视频1| 欧美一区二区视频在线观看| 国产欧美日韩精品a在线观看| 日日操操操| 久久久亚洲欧美综合|